© 2013 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 12/19/13
Axial Lead & Cartridge Fuses
3AB > High I
2
t > 328 Series
328 Series, Lead-Free 3AB, High Surge Withstanding Fuse
Agency Approvals
Features
• Highsurgewithstanding
capability
– 20 hits of 10kA 8/20μs
surge
– Meets ANSI/IEEE
C62.41, Category
C-High
– Meets US Dept of
Energy (DOE) MSSLC/
CBEA street lighting
and parking lot
lighting, elevated level
• Smallformfactor
(6.3×32mm) with
cartridge and axial-lead
package options
• Breakingcapacity:
200A@300VAC,
200A@100VDC
• Lead-free,RoHS
compliant, halogen-free
• CompliantwithUL248-
14 and NFPA 70
(NEC) primary fusing
requirements
• Operatingtemperature:
–55°C to 125 °
ApplicationsElectrical Characteristics for Series
Agency Agency File Number Ampere Range
T5026058201 21A
E10480 21A
% of Ampere Rating Opening Time
100%
4 hours, minimum
200%
120 sec., maximum
The – is a 300VAC rated, 10kA surge withstanding,
6.3×32mm ceramic fuse, designed in accordance to
UL248-14 Standard, provided in cartridge and axial-lead
packages.
Commercial and outdoor LED luminaries
Outdoor electronics and electrical equipment.
Surge protection for telecom application.
Description
Electrical Characteristic by ltem
Amp Rating
(A)
Voltage Rating
(VAC)
Interrupting
Rating
Surge
Rating
Nominal Cold
Resistance
(Ohms)
Nominal Melting
I
2
t (A
2
sec)
Agency Approvals
21 300
200A@300VAC
200A@100VDC
1.2/50 - 8/20µs,
20kV/10kA 20
hits
0.0042 4,800
X
X
Additional Information
Datasheet
Samples
Resources
Comentários a estes Manuais